| Castle Series C6KVA-C10KVA |
|
|
| |
High Frequency Online UPS Castle Series C6KVA-C10KVA |
|
|
| |
Servers, Data centers, Critical network devices, Sensitive electronic equipment, Telecom. |
|
 |
| |
The best charger design to recharge low battery as quickly as possible with out damaging batteries in 2 amp up to 8 amp and 240 VDC. Allowing 90% recharge in as little as 10 Hours after a total drain. Audible and Visual Over-load indicators: The incorporated LED over load indicator prevents ups overloads and premature failure of the UPS. N+1 Parallel Redundancy: Allows a 6 kva to grow upto 18kva or 12kva with 6 kva redundancy and a 20 kva to 60 kva or 40 kva with 20 Kva redundancy allowing user to add capacity as needed and lower investment. Simplified board separation: Dependent on the Units all operation are separated into 5 pcb boards allowing quick respond to damages and provides our valued dealers with simplified inventory and faster service to the end users. Dynamic Bypass: Automatic dynamic Bypass and manual Bypass provide a loop to repair UPS with out having to disconnect loads ideal for non stop computing for critical applications. SNMP Slot: Provides remote monitoring and control of UPS where a PC is not present or where this function is needed to be separated. IBM AS 400 Dry Contact card: Optional card to communicate in IBM AS 400 Protols Sine-wave output: True sine-wave output with a 3% THD on batteries. This feature provides dependable and compatible power for your most critical applications. True double conversion technology with zero Transfer Time: This advance design provides the closest you can get to Pure constant power in the industry. |
|
 |
 |
| Technical Specifications. |
High Frequency Online UPS Castle Series UPS C6KVA/C6KS C10KVA/C10KS 1.Output
| Output |
C6KVA/C6KS |
C10KVA/C10KS |
| Rated Power |
6000VA/4200W |
10000VA/7000W |
| Output Voltage |
208VAC/220VAC/230VAC/240VAC |
| Voltage Waveform |
Pure Sine wave |
| Crest Factor |
3:1 |
Output Frequency (Synchronized- Mains) |
46~54Hz or 56Hz - 64Hz (Line mode) 50/60HZ/ ±0.05Hz( Battery mode) |
| Regulation(Nominal) |
±1% |
| Regulation(Battery mode) |
±1% |
| Transfer time |
AC to DC :Zero Inverter to Bypass: Zero |
| Over current protection |
Line Mode:10min@100%~130%;Battery Mode:30s@100%~130% |
| Outlet |
Hard Wiring with Terminal Block |
| Harmonic Distortion |
≤2%THD(Linear Load);≤5%THD(Non-Linear Load) | 2.Input
| Nominal Voltage |
160~300VAC@full load (110~300VAC@half load) |
| Input Frequency |
46~54Hz / 56~60Hz |
| Efficiency |
90% (AC mode) 90%(Battery Type) |
| Noise Filtering |
Full time EMI/RFI filtering |
| Over current protection |
by AC fuse or by re-settable over current protector |
AVR Range (2 Bucks,2 Boosts) |
Enhanced Buck: +15% of selected nominal voltage Buck mode: +5% of selected nominal voltage Boost mode: -5% of selected nominal voltage Enhanced Boost: -12.5% of selected nominal voltage |
| Phase |
Single phase with ground | 3.Battery
| Battery type |
Sealed Lead Acid Battery |
| Rated Charging Voltage |
220.8Vdc |
| Typical backup time |
>5min |
| Charging method |
Smart pulse charging with two charging modes. Quick charging when battery is not fully charged, trickle charging when battery is 90% fully charged. |
| Charging current(MAX) |
1.0A(6KS,10KS:4.0/8.0A) |
| Protection |
Over current protection & Over charging voltage protection (SCR control) Thermal protection (CPU control) When temperature inside UPS is over 45℃,charger will stop charging for 2.5 minutes followed by an 1.5 minutes charging. The cycle will be repeated until the temperature is lower than 44℃. |
Temperature Compension |
Yes |
Numbers of Battery |
20 | 4.Optional Features
| ECO Mode |
Support |
| CVCF |
Support |
| PDU |
Support |
| Remote Panel |
Wired Type,Up to 100M Length |
| Parallel Redundancy |
Up to 4 Units maxium(Option) Up to 4 Units maxium(Option) | 5.Environmental and Safety
| Operating Temperature |
0℃ to 40℃ (32℉ to 104℉) |
Transit/storage Temperature |
-15℃ to 55℃ (5℉ to 131℉) |
| Relative Humidity |
20-90%(NON-CONDENSING) |
| Operating Altitude |
0 ~ 3000 meters |
| Audible noise |
≦50 dBA |
| Safety Markings |
BSMI |
CE |
| EMC |
Class B, EN50091-2, FCC part15, IEC1000-2-2 |
| Quality control system |
ISO 9001:2000 |
| Noise Level |
<60dB@1 Meter | 6.Indicator
| LED Version |
Load Level/Battery Level/Battery;Mode/AC Mode/Bypass Mode/Fault |
| Battery Mode |
Sounding every 4 seconds |
| Low Battery |
Sounding every second |
| Overload |
Sounding twice every second |
| Fault |
Continously Sounding | 7.Interface
| Smart RS-232 |
Software supports Windows Family.Sun Solaris, IBM Aix,Compaq True64,SGIIRIX ,FreeBSD.HP-UX,and MAC |
| USB (Option) |
Windows Family& MAC |
| Internal Slot (Option) |
SNMP/AS400 Relay Card/Rs485 |
| EPO(Option) |
Support Emergency Shutdown | 8.Physical
Dimensions: (D×H×W) |
570*260*717mm |
| N.W/G.W(kg) |
6KVA:90 6KS:35 |
10KVA:93 10KS:38 |
| Packing |
PBP standard Packing,Export carton for each unit | |
|
 |
|